Optional
Specifications
|
/ KS2
|
CENELEC ATEX (KEMA) Intrinsically safe approval
Applicable standard: EN 60079-0: 2006, EN 60079-11: 2007, EN 60079-26: 2007, EN 61241-0: 2006, EN 61241-11: 2006
Certificate: KEMA 06 ATEX0191
II1G Ex ia IIC T4 or T6, II1D Ex iaD
Amb. temp. for gas-proof T4: -40 to 850C (-40 to 1850F), T6: -40 to 600C (-40 to 1400F)
Surface temp. for dust-proof:
T4: T1050C amb. temp. -40 to 850C (-40 to 1850F)
T6: T850C amb. temp. -40 to 600C (-40 to 1400F)
Supply/output circuit: Ui=30V, Ii=120mA, Pi=0.84W, Ci=1nF, Li=10μH
Sensor circuit: Uo=9.6V, Io=25mA, Po=60mW, Co=2.4μF, Lo=33mH
|
/ DS2
|
FM intrinsically safe/Nonincendive and CENELEC ATEX intrinsically safe approval combination
(For CENELEC ATEX Intrinsically safe approval, see /KS2) [FM Intrinsically safe/Nonincendive approval]
Applicable standard: FM 3600, FM 3610, FM 3611, FM 3810
Intrinsically safe for Class I, Division 1, Groups A, B, C, and D
Supply : Vmax=28V, Imax=120mA, Pmax=0.84W, Ci三1nF, Li三10μH
Nonincendive for Class I, Division 2, Groups A, B, C, D
Hazardous (Classified) indoor/outdoor (TYPE 4) Locations
Supply: Vmax=35V, Imax=150mA, Ci=0μF, Li=10μH
Amb. temp.: T6 Ta=550C, T4 Ta=800C
|