Rosemount Field Communicator 475HP1EKLUGMTS
? Powerful fìeld diagnostics
? Bluetooth communication
? Long-Iasting Lithium-Ion power module
? Universal support for HART and FOUNDATION? fìeldbus devices
Introduction
Rosemount Field Communicator 475HP1EKLUGMTS
The 475 Field Communicator builds on the industry-Ieading technology of the 375 Field Communicator while adding innovative new capabilities including color displayBluetooth communication and advanced field diagnostics with applications like Valve Link? Mobile.
What you get is the most powerful handheld availabl universal user upgradeablintrinsically saferugged and liable. Only the 475 Field Communicator can deliver all this in a single handheld communicator.
Specifications
Rosemount Field Communicator 475HP1EKLUGMTS
Processor and Memory
Microprocessor: 80 MHz Hitachi SH3
Memory Internal Flash: 32 MB
System Card: 1 GB secure digital card
RAM: 32 MB
Physical
Weight: Approximately 1.65 lbs (0.75Kg) with battery
Display: ? VGA (240 x 320 pixels) color, 3.5 in (8.9 cm)
transflective display with anti-glare touch screen.
Keypad: 25 keys including 4 action keys, 12 alphanumeric keys, tab key, function key, backlight key, power key, and 4 cursor- control (arrow) keys; membrane design with tactile feedback.
Power Supply / Charger
Rosemount Field Communicator 475HP1EKLUGMTS
Battery: Rechargeable Lithium-Ion power module
Battery Operating Time:
20 Hours – continuous use
40 Hours – typical use
80 Hours – standby use
Battery Charger: Input Voltage 100-240 VAC, 50-60 Hz
Cables include US, European, and UK plugs
Connection
Battery Charger: Mini DIN 6-pin Jack
HART / Fieldbus: Three 4mm banana plugs (one common to
HART and Foundation Fieldbus)
IrDA Port: Supporting up to 115 kbps
+/- 15° maximum angle from center line
18 inches maximum distance
Bluetooth: 32.8 ft (10m) communication distance
Uses standard Windows drivers FCC, IC, and CE approvals
Environmental
Usage: +14°F (-10°C) to +122°F (+50°C)
0% to 95% RH (non-condensing)
{for +32°F (0°C) to +122°F (+50°C)}
Charge: +50°F (+10°C) to +104°F (+40°C)
Storage: With Batteries
-4°F (-20°C) to +131°F (+55°C)
Without Batteries
-4°F (-20°C) to +150°F (+60°C)
Enclosure Rating: IP51 (from front)
Shock: Tested to survive a 1 meter drop onto concrete
Shipping Weight
Shipping Weight: 5lbs (2.3Kg) (Varies by Option)
Easy Upgrade Requirements
Rosemount Field Communicator 475HP1EKLUGMTS
? PC with Internet access
? CD Rom drive
? IrDA port (or Adapter) or Bluetooth (or Adapter)
? SD Card Reader (required for some upgrades)
? Windows XP (SP2 or SP3) or Windows Vista Business (SP1)
475 Field Communicator Ordering Information
Rosemount Field Communicator 475HP1EKLUGMTS
Typical HART Model Number: 475HP1EKLUGMTS
Typical HART/Fieldbus Model Number: 475FP1EKLUGMTS