Manufacturer: Yokogawa Electric Corporation
Yokogawa Digital Indicator UM33A-000-10/DC
Features
? A 14-segment, active (PV display color changing function) color LCD display is employed.
Two five-digit, high-resolution displays are possible. Alphabet letters can be displayed in an easy-to-read manner. The guide display shows parameter names.
? Easy to operate
Navigation keys (SET/ENTER and Up/Down/Left/ Right arrow keys)are employed to facilitate making settings.
? 65 mm depth
The small depth enables the mounting in a thin and small instrumented panel.
Construction, Installation, and Wiring
Yokogawa Digital Indicator UM33A-000-10/DC
? Dust-proof and drip-proof: IP66 (for front panel)
? Material: Polycarbonate (Flame retardancy: UL94V-0)
? Case color: White (Light gray) or Black (Light
Charcoal gray)
? Weight: 0.5 kg or less
? External dimensions (mm): 96 (W) × 48 (H) × 65 (depth from the panel face)
(Depth except the projection on the rear panel)
? Installation: Direct panel mounting; mounting bracket, one each for left and right mounting
? Panel cutout dimensions (mm): 92+0.8/0 (W) × 45+0.6/0
(H)
? Mounting attitude: Up to 30 degrees above the horizontal. No downward titling allowed.
? Wiring: M3 screw terminal with square washer (for signal wiring and power wiring)
Power Supply Specifications and Isolation
Yokogawa Digital Indicator UM33A-000-10/DC
? Power supply:
Rated voltage:100 – 240 V AC (+10%/-15%), 50/60 Hz
24 V AC/DC (+10%/-15%) (for /DC option)
? Power consumption: 15 VA (DC: 7 VA, AC: 11 VA if
/DC option is specified)
? Data backup: Nonvolatile memory
? Power holdup time: 20 ms (for 100 V AC drive)
? Withstanding voltage
- Between primary terminals and secondary terminals: 2300 V AC for 1 minute (UL, CSA)
- Between primary terminals and secondary terminals: 3000 V AC for 1 minute (CE)
- Between primary terminals: 1500 V AC for 1 minute
- Between secondary terminals: 500 V AC for 1 minute
(Primary terminals: Power (*) and relay output
terminals; Secondary terminals: Analog I/O signal terminals, contact input terminals, communication terminals, and functional grounding terminals.)
(*): Power terminals for 24V AC/DC models are the secondary terminals.
? Insulation resistance
Between power supply terminals and a grounding terminal: 20 MΩ or more at 500 V DC
Environmental Conditions
Normal Operating Conditions
Yokogawa Digital Indicator UM33A-000-10/DC
? Ambient temperature: -10 to 50oC
? Ambient humidity: 20 to 90% RH (no condensation allowed)
? Magnetic field: 400 A/m or less
? Continuous vibration at 5 to 9 Hz: Half amplitude of
1.5 mm or less, 1oct/min for 90 minutes each in the three axis directions
Continuous vibration at 9 to 150 Hz: 4.9 m/s2 or less, 1oct/min for 90 minutes each in the three axis directions
? Short-period vibration: 14.7 m/s2, 15 seconds or less
? Shock: 98 m/s2 or less, 11 ms
? Altitude: 2000 m or less above sea level
? Warm-up time: 30 minutes or more after the power is turned on
? Startup time: Within 10 seconds
*: The LCD (a liquid crystal display) is used for a display portion of this product.
The LCD has a characteristic that the display action becomes late at the low temperature.
Model and Suffix Codes
Yokogawa Digital Indicator UM33A-000-10/DC
Model
|
Suffix code
|
Optional suffix code
|
Description
|
UM33A
|
|
|
Digital Indicator with Alarms (provided with retransmission output or 15 V DC loop power supply, 2 DIs, and 3 DOs) (Power supply: 100-240 V AC)
|
Type 1: Basic
|
-0
|
|
|
|
|
|
Standard type
|
Type 2: Functions
|
0
|
|
|
|
|
None
|
1
|
|
|
|
|
1 additional DO (c-contact relay), RS-485 communication (Max.38.4 kbps,
2-wire/4-wire)
|
2
|
|
|
|
|
1 additional DO (c-contact relay)
|
3
|
|
|
|
|
6 additional DOs (c-contact relay; 1 point and open collector; 5 points)
|
Type 3: Open networks
|
0
|
|
|
|
None
|
Display language (*1)
|
-1
|
|
|
English
|
-2
|
|
|
German
|
-3
|
|
|
French
|
-4
|
|
|
Spanish
|
Case color
|
0
|
|
White (Light gray)
|
1
|
|
Black (Light charcoal gray)
|
Optional suffix codes
|
/LP
|
24 V DC loop power supply (*2)
|
/DC
|
Power supply 24 V AC/DC
|
/CT
|
Coating (*3)
|
*1: English, German, French, and Spanish can be displayed as the guide display.
*2: The /LP option can be specified only when the code for Type 2 is "0", "1" or "2." Additionally, the RS-485 communication for
“1” of the Type 2 code is 2-wire system.
*3: When the /CT option is specified, the UM33A-000-10/DC does not conform to the safety standards (UL and CSA) and CE marking.