Yokogawa Centum VP, Yokogawa DCS
Yokogawa Optical ESB Bus Node Unit ANB11D-B25/BU2A
Node Unit for Dual-Redundant ESB Bus with Optical Repeater (for AFV30?/AFV40?)
The ESB Bus Node Unit has an interface function that communicates the analog I/O signals and contact I/O signals of a ?eld with a Field Control Unit (FCU) via an ESB bus, as well as a function that supplies power to the I/O Modules.
This node units are connected to FCU via an ESB bus.
Yokogawa Optical ESB Bus Node Unit ANB11D-B25/BU2A
Hardware Specifications
Node Connection
When connecting an ESB Bus Node Unit to FCU, install ESB Bus Couple Module (EC401 or EC402) to FCU (*1).
EC401 or EC402 must be installed in slot 7 and slot 8. To make single configuration, EC401 or EC402 must be installed in slot 7, and slot 8 must be empty.
*1: AFV30 , AFV40 , AFV10 , or AFF55 .
Power Supply
Yokogawa Optical Repeater Dual-Redundant ESB Bus Node Unit ANB11D-225/BU2B Yokogawa Optical ESB Bus Node Unit ANB11D-B25/BU2A
Specify with Suffix Codes
Voltage: 100-120 V AC, Frequency: 50/60 Hz
Voltage: 220-240 V AC, Frequency: 50/60 Hz
Voltage: 24 V DC
Electric Power Consumption
Yokogawa Optical ESB Bus Node Unit ANB11D-B25/BU2A
100-120 V AC: 200 VA, 120 W
220-240 V AC: 230 VA, 120 W
24 V DC: 5.5 A
l Weight
10 kg (including 8 I/O Modules)
Mounting
19-inch Rack Mounting
Rack mount (M5 x 4 screws)
Insulation bash (accessory)
Regulatory Compliance
Yokogawa Optical ESB Bus Node Unit ANB11D-B25/BU2A
Safety Standards
[CSA] (for 100-120 V AC and 24 V DC power supply)
[CE Marking] (for 100-120 V AC, 220-240 V AC and 24 V DC power supply)
EMC Conformity Standards
[CE Marking] (for 100-120 V AC, 220-240 V AC and 24 V DC power supply)
[C-Tick Marking] (for 220-240 V AC and 24 V DC power supply)
[KC Marking] (for 100-120 V AC, 220-240 V AC and 24 V DC power supply)
Standards for Hazardous Location Equipment
[CSA Non-Incendive] (for 100-120 V AC and 24 V DC power supply)
[FM Non-Incendive] (for 100-120 V AC, 220-240 V AC and 24 V DC power supply)
[Type n] (for 24 V DC power supply)